Posted by: Pdfprep
Post Date: December 17, 2020
When using a UPS5000-E (50 kVA power module) with the actual load of 160 kW, 1+1 rack redundancy, and single UPS backup solution, each rack uses three battery strings, each battery string consists of 40 batteries, and the main switch box capacity is ().
A . 250 A
B . 320 A
C . 500 A
D . 630 A
Answer: C
Leave a Reply